Circular Chart Recorder
– CR6” Open Frame
The 6” Open Frame Circular Chart Recorder for OEMs is part of G-Tek’s most popular series, CR2010 Pro, offering utmost reliability and versatility at an affordable price. The pressure pen eliminates concerns about ink depletion or pen replacement. Pressure-sensitive papers are used instead of thermal papers to ensure that the marking is retained for a longer period. These chart plate recorders are widely used in low-temperature equipment, blood banks, incubators, and many more places. It takes direct inputs from RTD Pt-100. Standard chart speeds available are 1 day/ 7 days/ 31 days per revolution. These recorders are microcontroller-based. The crystal-controlled chart drive ensures accurate chart speed. Stepper motors for both pen and chart drive ensure no lag and no backlash. With a cutout of 191 x 163 mm and the smallest depth, it is very convenient to use. They come with a universal power supply as a standard feature. A clamp option is also available that holds panels securely, allowing for easy installation and removal.
Features
- 6” Chart Width
- Inkless Chart Recorder
- Pressure Sensitive Paper for long retention of data
- Single Analog Input channel
- Direct Input Standard Pt-100 sensors
- Universal Power Supply 85-264 V AC, 47-63 Hz
- Battery Backup of more than 7 day*
- Available chart speed of 1D, 7D, 31D / Rev
- Fitting Clamp
* Battery life is calculated assuming process parameter does not vary more than 0.15 Deg/Min and recorder is not turned OFF or ON And the sensor input is not alarming condition. (Battery life depends on number of times recorder on/off and sensor input Variation and alarm condition.)
Specification
Model No | CR-2010 Pro Series Circular Chart Recorder |
Product code | 9994x-xx001 |
Pens | |
No. of Pens | 1 |
Pen marking | Continuous |
Pen Response Time | < 10 Sec. (Full Scale) |
Pen Resolution | Stepper Motor Controlled better than 0.1% FSD |
Overshoot | None |
Chart | |
Chart Speed | In day mode — 1 day/ 7 days/ 31days per revolution |
User setting | User programmable |
Chart Calibrated Radius/ Size | 2.3 ” (calibrated radius approx. 59 mm) / Circular, 5.51″ (140 mm) |
Chart Ranges | Refer Table 1 and Table 2 |
Display, Operator Panels and Inputs | |
Display Type | None |
Status Indicators | ALM LED – Red LED blinking indicates Alarm high/low condition
BAT LED – Green LED blinking indicates Normal Operation
Red LED blinking indicates Battery Low status Yellow LED blinking indicates Error condition |
Panel Keys | Front panel Keyboard consisting of three keys for configuration and calibration |
Number of Analog Input | 1 |
Analog Input (Sensor) | RTD (PT-100) |
Sensor Type and Range | Refer to Table 3 |
Scan Rate | Mains + Battery: Continuous 1 reading per 2 seconds for 1 Day, 7 Days and 31 Days chart speed |
Protection | |
Input Impedance RTD | > 20 MΩ |
CMRR | > 115 dB @ 50, 60 Hz at 20 sample per second |
NMRR | > 88 dB @ 50, 60 Hz at 20 sample per second |
Maximum Common Mode Voltage | 5V AC |
Isolation Channel-EARTH | NA |
Input Protection | 30V AC/DC Max
|
Environmental | |
Temperature | (Operation) +5˚C to +45˚C
(Limiting) 0˚C to +50˚C. (Storage) -20˚C to +60˚C |
Humidity | (Operation) 10 to 80 % RH Non-Condensing
(Storage) 5 to 90 % RH Non-Condensing |
Altitude | <2000 meter |
Power Requirement | |
Mains Supply + Internal Battery Model
|
Power Supply: 85 to 264 VAC ,47-63 Hz.
Battery: 2×1.5 VDC Ultimate Lithium Non rechargeable battery 3500 mAh |
Power Rating | 3 V, 300 mA (Max) ; 1 W Max with maximum configuration |
Fuse Type | None |
Battery Reverse Polarity | Protected |
Battery backup | 7 days** |
Standards | |
EMI-EMC | IEC 61000-6-2/6-3 |
Safety | IEC 61010-1 |
Pollution Degree | II |
Installation Category | II |
Vibration | 2g Peak (10Hz-150Hz) |
Shock | IEC 61010-1 |
Physical Characteristics | |
Overall Dimensions Max
L x W x D (mm) |
191 x 163 x 66 mm |
Weight | Approx. 1 kg (with Sensor and battery) |
Mounting | Panel Mount |
** Battery life is calculated assuming process parameter does not vary more than 0.15 Deg/Min and recorder is not turned OFF or ON And the sensor input is not alarming condition. (Battery life depends on number of times recorder on/off and sensor input Variation and alarm condition.)
Table 1- Programmable Chart Ranges
Chart Type
xx |
Chart Range*** |
01 | +50 to -50 |
02 | +50 to -100 |
03 | +40 to -10 |
04 | -50 to +50 |
05 | -10 to +32 |
06 | +32 to -10 |
07 | +34 to -50 |
08 | -10 to +40 |
09 | -10 to +15 |
10 | -10 to +50 |
11 | 0 to 150 |
12 | -6 to -90 |
13 | 0 to 100 |
14 | 0 to 300 |
15 | +30 to -40 |
16 | 0 to +50 |
*** First value in the chart range is at the center of the chart.
Table 2- Available Chart(s) and their ranges
21Chart Type
xx |
Range*** | Part Description |
41 | 0 to + 50 (PS) | W6 0 +50 PS |
42 | +30 to -40 (PS) | W6 +30 -40 PS |
43 | -40 to +25 (PS) | W6 -40 +25 PS |
44 | -115 to +50 (PS) | W6 -115 +50 PS |
45 | -200 to 0 (PS) | W6 -200 0 PS |
46 | 0 to +60 (PS) | W6 0 +60 PS |
Others, Please Specify |
Sensor Type | Valid Input Range | Resolution | Accuracy | Linearization Error |
Pt-100 (RTD)# | -200 to 850 °C | 1 % | ± 0.5 % FSD | ± 0.06 °C Max |
Table 3- Sensor Type and Range
# α = 0.00385
Accessories
Circular Chart Pack of 30 : 1 (Refer Table 2 for the chart range and part no.)